Back to Articles

Thorhildur Edda Gunnarsdottir, CEO

Published

Updated

Hotel legionella prevention: a maintenance guide

Hotel legionella prevention: a maintenance guide

Hotels in the Netherlands must run a legionella risk analysis, a management plan, a logbook and six monthly sampling. This guide shows how maintenance and housekeeping turn that plan into reliable daily routines.

Hotel legionella prevention: a maintenance guide

In short

• RIVM lists hotels and guesthouses as priority locations for legionella prevention in the Netherlands. • A BRL 6010 certified company must make the risk analysis and the legionella management plan. • Hotels must keep a logbook of measures taken and have the water sampled every six months. • Results above 1,000 colony forming units per litre must be reported to the ILT within 48 hours. • Flushing unused rooms, temperature checks and descaling showers work best as recurring tasks with a named owner.

Hotel legionella prevention means a risk analysis of your water system, a management plan based on it, routine checks such as flushing taps and recording temperatures, and a logbook that proves every measure was carried out. Sweeply helps maintenance teams turn that plan into recurring tasks with a clear owner, so the checks happen on time and the records are ready when an inspector asks.

Legionella is a maintenance topic that guests never see until something goes wrong. A hotel has long pipe runs, rooms that stand empty for days, showers that create fine spray and hot water systems that rarely run at one steady temperature. Those are exactly the conditions the bacteria like. This guide explains what hotels in the Netherlands are required to do, how to turn the management plan into daily work, and where the routine usually breaks down.

Disclosure: Sweeply sells hotel maintenance software and housekeeping software. The legal points below are linked to public Dutch government sources; check the current rules for your own building with a certified adviser.

Is legionella prevention mandatory for hotels in the Netherlands?

Yes. The Dutch public health institute RIVM lists buildings with an accommodation function, including hotels and guesthouses, as priority locations for legionella prevention, alongside hospitals, swimming pools and campsites. The government business portal Ondernemersplein describes the same obligation for hotels, bed and breakfasts and guesthouses with more than five sleeping places.

For those locations the rules set out a clear sequence of duties:

  • Have a risk analysis of the water installation made by an adviser with a BRL 6010 certificate.

  • Have a legionella management plan drawn up on the basis of that risk analysis, again by a BRL 6010 certified company, and carry it out.

  • Keep a logbook that records which measures were taken and when.

  • Have the water sampled for legionella every six months by a recognised sampler.

  • Report to the Human Environment and Transport Inspectorate (ILT) within 48 hours when a sample shows more than 1,000 colony forming units per litre, and take the measures from your management plan when results fall between 100 and 1,000.

Ondernemersplein refers to the Drinking Water Decree, the Drinking Water Regulation and the regulation on legionella prevention in drinking water and hot tap water as the legal basis. Belgium and other countries have their own rules, so a hotel group with properties in several countries needs one plan per building and per jurisdiction.

Why are hotels a higher legionella risk than other buildings?

Legionella bacteria grow in water between 25 and 55 degrees Celsius, as Ondernemersplein explains. Infection happens when people breathe in fine droplets, which is why showers, spa baths and pool areas matter more than a glass of tap water. Hotels combine several risk factors in one building:

Risk factor

Where it shows up in a hotel

Typical routine measure

Stagnant water

Rooms out of order or unsold for days, closed wings, seasonal annexes

Flush taps and showers in unused rooms on a fixed schedule

Lukewarm water

Long pipe runs, poorly insulated risers, mixing valves set too low

Record hot and cold water temperatures at agreed points

Spray and aerosols

Showers, spa baths, pool showers, humidifiers

Clean and descale shower heads and hoses periodically

Dead legs

Disconnected pipes after a renovation, removed bathroom fittings

Find and remove them, as identified in the risk analysis

Many people, changing every day

Guests, staff, events and wellness visitors

Keep the logbook complete so the plan can be shown to be working

Pools and hot tubs need their own controls on top of the tap water plan. Our guide to hotel pool maintenance problems covers water testing and the technician checklist for that part of the building.

What does a legionella management plan ask your team to do?

The certified adviser writes the plan, but your own team carries it out every week. Most plans translate into a short list of recurring jobs. The exact frequencies and measuring points come from your own risk analysis; the table below shows how hotels usually organise the work.

Task

Who usually does it

How often (as set in your plan)

Flush taps and showers in rooms not used in the period set by the plan

Housekeeping or maintenance

Weekly, or as the plan specifies

Record water temperatures at the agreed tapping points

Maintenance technician

Weekly or monthly

Clean and descale shower heads and hoses

Housekeeping with maintenance

Periodically, for example quarterly

Check the boiler, buffer tank and circulation pump

Maintenance or installer

Monthly and at annual service

Arrange sampling by a recognised sampler

Head of maintenance

Every six months

Review the logbook and act on deviations

Head of maintenance or general manager

Monthly

If your building already has a hotel preventive maintenance schedule, these tasks belong in it rather than on a separate sheet in the plant room. One plan for the whole building is easier to follow and easier to audit.

Where does legionella prevention break down in a busy hotel?

Few hotels ignore legionella on purpose. The routine fails in small, ordinary ways that add up over a season:

  • The flushing list is printed once a week, but rooms go out of order or stay unsold after it was printed, so the rooms that most need flushing are missing from it.

  • Temperatures are written on a paper form in the plant room and only reviewed when the adviser visits.

  • A housekeeper notices a shower that runs lukewarm, mentions it at the end of a shift and the remark never reaches a technician.

  • The technician who knows the system is on holiday, and nobody else knows which tapping points to measure.

  • Housekeeping and maintenance speak different languages, so instructions are shortened or misunderstood.

Most of these are coordination problems, not technical ones. Our guide to housekeeping and maintenance coordination covers the handover between both teams, and the article on hotel maintenance fault reporting explains how to make sure a lukewarm shower is reported once and followed up.

How does maintenance software support legionella prevention?

Software does not replace the risk analysis, the certified adviser or the laboratory. What it does is make sure the routine in the management plan actually happens and leaves a record. In Sweeply Maintenance that looks like this:

  • Recurring preventive tasks: flushing rounds, temperature checks and descaling appear automatically on the right person's phone at the frequency your plan sets.

  • Resolution history per room: every completed task is kept with date, unit and owner, so the record of what was done and when is complete.

  • Photo fault reports: a housekeeper who finds a lukewarm shower or a leaking tap reports it from their phone with a photo and location, and it is routed to the right technician.

  • Full issue log and one click export: the record can be exported when your adviser or an inspector asks for it.

  • 30+ languages: housekeepers and technicians each read the same instruction in their own language.

Volkshotel in Amsterdam, 196 rooms with a team of 33 nationalities, runs Sweeply on Mews and reports faster repairs, as described in the Volkshotel case study. Hotels on Mews in the Netherlands and Belgium can connect through the Sweeply Mews integration, and Sweeply Maintenance can also start on its own before the PMS is connected. Lifestyle Hotel Vitar uses photo fault reports and one shared task overview on Rentlio, as the Hotel Vitar case study shows.

Because Sweeply also runs hotel housekeeping software on the same platform, a room that goes out of order or stays empty is visible to both teams, which makes it easier to plan flushing for the rooms that need it.

What should a legionella checklist for technicians include?

  1. Unused rooms: every tap and shower in rooms that were not used during the period in your plan has been flushed, and the flush is recorded.

  2. Temperatures: hot and cold water measured at the agreed tapping points, recorded with the time, and any reading outside the plan reported at once.

  3. Showers: shower heads and hoses on the descaling schedule have been cleaned, and damaged ones replaced.

  4. Plant room: boiler, buffer tank and circulation pump checked as the plan specifies, with any fault logged.

  5. Changes to the building: renovations, removed fittings or closed sections reported to the head of maintenance, because they can create dead legs and may require the risk analysis to be updated.

  6. Sampling: the next six monthly sample is booked and the last result is filed with the logbook.

Where this guide does not apply

  • Designing or changing the water installation itself, which belongs with a certified installer and your BRL 6010 adviser.

  • Writing the risk analysis or management plan, which Dutch rules require a certified company to do.

  • Cooling towers, wet cooling installations and other systems with their own legal requirements.

  • Hotels outside the Netherlands, where national or regional rules set different duties and thresholds.

  • Medical advice or an active outbreak, where the ILT, the municipal health service and your adviser lead.

Talk to our sales team

If you want to see how flushing rounds, temperature checks and fault reports can run as tracked tasks across your hotel, Book a call with our sales team.

Conclusion

Legionella prevention in a hotel depends less on the plan on paper than on the weekly routine behind it: flushing unused rooms, recording temperatures, reporting faults and keeping the logbook complete. Give every task in the plan an owner and a record, and the next inspection becomes a formality.

Frequently asked questions

Is legionella prevention mandatory for hotels?

In the Netherlands, yes. Hotels, bed and breakfasts and guesthouses with more than five sleeping places are priority locations and need a risk analysis, a management plan, a logbook and water sampling every six months.

Who must make the legionella risk analysis for a hotel?

The risk analysis and the management plan must be made by a company with a BRL 6010 certificate. The hotel team then carries out the measures and records them in the logbook.

How often should taps be flushed in unused hotel rooms?

Your management plan sets the frequency for each part of the building. Many hotels schedule flushing weekly for rooms that have not been used, and record each flush in the logbook.

What happens if a legionella sample is too high?

Above 1,000 colony forming units per litre the hotel must report to the ILT within 48 hours. Between 100 and 1,000 the measures in the management plan apply.

Can maintenance software replace a legionella management plan?

No. Software does not replace the certified risk analysis or plan, but it schedules the recurring tasks, routes faults to technicians and keeps a dated record of every measure.